In an effort to help cut down the likelihood of failed inspections, and the associated re-inspections and re-inspection fees, we are providing you with a list of often-found building code violations.
Common violations found on ROUGH building inspections:
- Penetrations through the top and bottom plate.
- Proper stud guards shall be installed where drywall screws and nails can penetrate PVC, conduit, water piping and the like.
- The proper connectors for uplift on rafters.
- The proper location of smoke detectors/carbon monoxide detectors.
- Installation of the Ufer ground for new single family homes.
- The installation of a one inch conduit run from the basement to the attic (local amendment).
- The installation of the electrical box for future use of an active Radon system (State of Illinois Requirement).
- Proper sealing of electrical boxes on the exterior walls for energy code compliance.
- Properly sized vent and drain plumbing lines.
- Over boring of studs in exterior and interior walls.
Common violations found on FINAL building inspections:
- Proper installation of handrails.
- Proper installation of guard rails.
- Smoke detectors installed in proper location and operational in series.
- Carbon monoxide detectors installed in proper location.
- The water and gas piping shall be bonded at the water heater.
- The electrical disconnect for the dishwasher shall be located in a visible location.
- The Building Compliance Sticker shall be filled out properly and located in the electrical panel.
- The electrical panel shall have all circuits properly labeled.
- The results of a door blower test shall be provided to the Village prior to a final inspection being conducted.
- Inoperable GFCI receptacle.
- The overcurrent protection for the A/C unit must not exceed the name plate rating.
- The service door from the garage into the house must have a closer.
- All penetrations to the exterior must be sealed.
- The attic scuttle hole must have a gasket.
- Beam pockets in the basement must be grouted.
- Bolts in the basement or elsewhere must be tight to the column.
- Project must be 100% complete prior to the inspection taking place. It should be ready for the homeowner to occupy.
- A vacuum breaker is required on handheld showers.
- The water temperature must be a minimum of 120 degrees at the kitchen sink and shall not exceed 115 degrees at tubs and showers.
- The dishwasher cannot discharge into the garbage disposal.
- The garbage disposal must be trapped separately from all other compartments.
- A proper sized expansion tank is required on all closed water systems.
- The ejector pit shall be properly sealed with proper ball and check valve.